HNPQAF,HNPQSG系列有源滤波器、无功补偿器是是哪家的?
深圳市慧能互联科技有限公司,
有源滤波器(APF)型号:HNPQAF150-4W1, HNPQAF100-4W1, HNPQAF050-4W1, HNPQAF150-3W1, HNPQAF100-3W1, HNPQAF050-3W1, HNPQAF150-4M1, HNPQAF100-4M1, HNPQAF050-4M1, HNPQAF150-4M0, HNPQAF100-4M0, HNPQAF050-4M0, HNPQAF150-3M1, HNPQAF100-3M1, HNPQAF050-3M1, HNPQAF150-3M0, HNPQAF100-3M0, HNPQAF050-3M0
无功补偿(SVG)型号:HNPQSG150-4W1, HNPQSG100-4W1, HNPQSG050-4W1, HNPQSG150-3W1, HNPQSG100-3W1, HNPQSG050-3W1, HNPQSG150-4M1, HNPQSG100-4M1, HNPQSG050-4M1, HNPQSG150-4M0, HNPQSG100-4M0, HNPQSG050-4M0, HNPQSG150-3M1, HNPQSG100-3M1, HNPQSG050-3M1, HNPQSG150-3M0, HNPQSG100-3M0, HNPQSG050-3M0 。
商业机机柜类HN-PQSC-270/9-400V:
SVC无功补偿柜-总容量270kVar-9支路-400V
HN-PQAF-300/3-4:APF动态补偿柜-300A-3模块-三相四线-400V
HN-PQAF-200/3-4:APF动态补偿柜-200A-3模块-三相四线-400V
HN-PQAF-500/3-4:APF动态补偿柜-500A-3模块-三相四线-400V
官网:www.hnergy.com
不知力率起点在那开始补偿,如在0.8提高至0.95(标准为0.9),每KW功率需电容器补偿量为0.421千乏,那么:615×0.421≈259(千乏)
用BZMJ-0.45-18-3电容器10组:18×10=180(千乏),显然不够。
需要电容器组数:259/18≈14(组)
最好用14组BZMJ-0.45-18-3电容器,以防容量的减退或部分损坏。
如果按标准0.9算,每KW功率需电容器补偿量为0.266千乏,那么:
615×0.266≈164(千乏)
164/18≈9(组)
如果力率从0.75提高至标准0.9算,每KW功率需电容器补偿量为0.398千乏,那么:615×0.398≈245(千乏)
245/18≈14(组)
也可按照安装方式、补偿速度、投切元件,补偿或滤波等分类命名
svg柜是高压柜子。
SVG是典型的电力电子设备,由三个基本功能模块构成:检测模块、控制运算模块及补偿输出模块。其工作原理为由外部CT检测系统的电流信息,然后经由控制芯片分析出当前的电流信息、如PF、S、Q等;
然后由控制器给出补偿的驱动信号,最后由电力电子逆变电路组成的逆变回路发出补偿电流。国际上最先进的SVG产品是STATCOM静态无功补偿装置。
尺寸,这个很重要,首先你要确定现场能留多少位置给你放置补偿柜。
容量,最基本要求,起码得满足功率因数的正常需求。
单段补偿量大小:根据系统的情况决定,是否存在空载,轻载,日常运行状况如何,这些都需要了解才能决定你的补偿方案。
电抗率:根据系统谐波状况选择合适的电抗率以抑制谐波,主要有3次(14.8),5次(6%)两种。3次经常应用在建筑类场合,适用单相负荷较多状况。5次应用在工矿企业。
当然,在设计的时候经常会有业主要求推荐几个厂家,这就涉及到产品定位,是使用进口品牌,合资品牌,还是国产?所以最好是多了解接触目前市场的补偿厂家。对平时的设计工作也会有帮助的。